3.4.20 “PA” AC Current Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
If input current value exceeds the set protection value, then it can be judged that AC current protection
occurs and system will shut down for protection.
Possible reason:
System is heavy-loaded and compressor current is too large.
Grid voltage is abnormal.
PFC module is damaged.
Drive board PFC current sampling circuit element is damaged or drive chip PFC current sampling AD terminal is
abnormal.
Troubleshooting
:
3.4.21 “Pc” Driver Current Error
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
After power charging, if offset voltage average is detected to exceed 12.5% of 1.65V in 1s, then it can be
judged that current detection (or current sensor) circuit is faulted. System will shut down for protection.