Level 3
2.3.5 Forced Defrost Control
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
switching to "06", short press "SW2" or "SW3" to enter the forced defrosting mode, "ON" means open, "OF"
means close, and then short press "SW1" to save. During debugging, if no operation is performed within 10s, the
debugging mode interface will be exited.
2.3.6 Refrigerant Recovery Control
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
switching to "08", short press "SW2" or "SW3" to enter the refrigerant recovery control mode, "ON" means open,
"OF" means close. And then short press "SW1" to save. During debugging, if no operation is performed within
10s, the debugging mode interface will be exited.
2.3.7 Forced Operation Control
Press and hold "SW1" for about 5s to enter the first level menu of the debugging mode, the outdoor unit
mainboard LED displayer flashes. Under the first level menu, short press "SW1" to switch various functions. After
Capacity
48K indoor unit dip switches
60K indoor unit dip switches
Level 1
(Default)
Level 2
Level 3
12