When the separator is detached, check whether there are impurities inside. Below is the checking method:
NOTE:
When pouring the liquid from the separator, make sure the discharge pipe is at the lower position.Slant at an
angle not larger than 20°
Use a transparent container to collect the content inside the separator. Check its color, seal it well and return
it to the factory for inspection.
NOTE:
If the compressor is damaged and needs to be replaced, the gas-liquid separator should also be replaced,
whether or not there are impurities in the separator or other abnormal conditions.
Confirm which parts of the system should be replaced. Make sure the pipe mouths of the damaged parts or
components are sealed by adhesive tape as soon as they are detached. Keep them in the original condition for
future analysis.
Step 7: Clear the pipeline
After confirming which parts of the system should be replaced, check the pipeline of the system. Blow
through the main pipeline with nitrogen. After clearing the pipeline, if the components are not replaced
immediately, seal the pipeline with adhesive tape to prevent the system from being contaminated by water and
impurities in the air.
2. Remove the screw bolt of
the separator.
1. Remove the screw bolt of
the separator.
3. Remove the separator.
66
SERVICE MANUAL
Summary of Contents for Inverter FLEX24 DEV24H2R18
Page 9: ...6 SERVICE MANUAL 2 Control 2 1 Operation Mode 2 1 1 Cooling Mode ...
Page 10: ...2 1 2 Heating Mode SERVICE MANUAL 7 ...
Page 19: ...Model DEV48H2R18 DEV60H2R18 16 SERVICE MANUAL ...
Page 27: ...SEV2040H2R18 SEV4060H2R18 24 SERVICE MANUAL ...