Page 15
Omni Installation Instructions
© Mass Electronics Pty Ltd 2017
Chapter 1 – Preliminary Information
1-3 Special Considerations
The following precautions and installation considerations must be observed to ensure personal
safety and to prevent damage to equipment:
•
Local safety regulations, building codes and ordinances must be complied with during
installation. In cases of conflict with procedures in this manual, contact Innotech or its authorised
representative for clarification.
•
To prevent damage to equipment, avoid applying electrical power to the equipment prior to
checking the system, unless specifically instructed to do so in this manual.
•
The Omni System can be installed using common tools and test equipment. Only qualified
personnel familiar with local codes and practices should install the system. Wiring should only be
performed by someone knowledgeable of electronics and wiring installation practices. Refer to the
appropriate documentation when installing items provided by other manufacturers.
1-4 Installation Plans
The following installation items should be gathered and made available to the installation team:
•
This technical manual.
•
Computer-Generated Wiring Diagram: the Innotech Focus software can be used to print a wiring
diagram for the specific application.
•
For non-Innotech equipment, gather the manufacturer’s installation-related data such as
schematics, wiring diagrams, dimension diagrams, etc.
•
Any other data source as it becomes known.
1-5 Tools and Test Equipment
A 2mm flat blade screwdriver is required for wiring of the terminals. A high impedance digital
Multimeter is the only item of electronic test equipment required.
Specification
Omni C40
Omni C20
Omni C14
Omni U10
Processor Speed
800MHz
800MHz
600MHz
72MHz
Programmable Points (UI/O)
40
20
14
10
Non Volatile Memory
128KB
128KB
8KB
-
Real-time Clock
Yes
Yes
Yes
-
RS-485 Ports
3
3
2
1
Ethernet - 100BASE-T
2
2
1
-
8GB MicroSD for Logging (32GB max.)
Yes
Yes
Yes
-
HMI (on-board)
Optional
Optional
Optional
-
HMI (External)
Optional
Optional
-
-
USB-A (Host)
Yes
Yes
-
-
USB-Mini B (PC Link)
Yes
Yes
Yes
Yes
PC Link Speed
480Mbps
480Mbps
480Mbps
12Mbps
ISS RS-485 Comms
Yes
Yes
-
-
Status LED
Yes
Yes
Yes
Yes
Field Supply 24VDC
Yes
Yes
-
-
Expansion Port
Yes
Yes
-
-
UI/O Point Processing Limit
90
70
14
N/A
Omni U10 Support (Total Devices)
5
5
-
-
Web Server
Yes
Yes
Yes
-
Protocol Routing
Yes
Yes
Yes
-
BACnet Broadcast Management Device
Yes
Yes
Yes
-
Max. UI/O Power
0.5W
0.5W
0.5W
0.5W
Max. IO System Power
18W
10W
4.5W
4.5W
Summary of Contents for Omni C14
Page 1: ...Omni INSTALLATION INSTRUCTIONS...
Page 11: ...Omni INSTALLATION INSTRUCTIONS Preliminary Information 1...
Page 17: ...Omni INSTALLATION INSTRUCTIONS Mechanical Installation 2...
Page 31: ...Omni INSTALLATION INSTRUCTIONS Electrical Installation 3...
Page 53: ...Omni INSTALLATION INSTRUCTIONS Networking 4...
Page 74: ...Omni INSTALLATION INSTRUCTIONS Commissioning 5...