Omni Installation Instructions
Page 14
© Mass Electronics Pty Ltd 2017
Edition 1.2 dated 16.08.2018
1-2 Specifications Table
Specification
Omni C40
Omni C20
Omni C14
Omni U10
Processor Speed
800MHz
800MHz
600MHz
72MHz
Programmable Points (UI/O)
40
20
14
10
Non Volatile Memory
128KB
128KB
8KB
-
Real-time Clock
Yes
Yes
Yes
-
RS-485 Ports
3
3
2
1
Ethernet - 100BASE-T
2
2
1
-
8GB MicroSD for Logging (32GB max.)
Yes
Yes
Yes
-
HMI (on-board)
Optional
Optional
Optional
-
HMI (External)
Optional
Optional
-
-
USB-A (Host)
Yes
Yes
-
-
USB-Mini B (PC Link)
Yes
Yes
Yes
Yes
PC Link Speed
480Mbps
480Mbps
480Mbps
12Mbps
ISS RS-485 Comms
Yes
Yes
-
-
Status LED
Yes
Yes
Yes
Yes
Field Supply 24VDC
Yes
Yes
-
-
Expansion Port
Yes
Yes
-
-
UI/O Point Processing Limit
90
70
14
N/A
Omni U10 Support (Total Devices)
5
5
-
-
Web Server
Yes
Yes
Yes
-
Protocol Routing
Yes
Yes
Yes
-
BACnet Broadcast Management Device
Yes
Yes
Yes
-
Max. UI/O Power
0.5W
0.5W
0.5W
0.5W
Max. IO System Power
18W
10W
4.5W
4.5W
Table 1-2:
Specifications Table
• The real-time clock battery is user replaceable but should only be replaced by qualified Innotech service
technicians or distributors. The battery is located in the expansion bay on all controller models.
• The controller's MicroSD card also contains PDF documents. For the latest documents, visit
• The optional on-board HMI module can only be installed by qualified Innotech service technicians.
• Omni U10 Remote Expansion Modules add 10 points for each U10 used.
Eg: An Omni C40 with 5 U10's will support 90 points total (40 [C40] + 50 [5 x U10's]).
• Not all controllers support the U10, see the table above for support and device limits.
Summary of Contents for Omni C14
Page 1: ...Omni INSTALLATION INSTRUCTIONS...
Page 11: ...Omni INSTALLATION INSTRUCTIONS Preliminary Information 1...
Page 17: ...Omni INSTALLATION INSTRUCTIONS Mechanical Installation 2...
Page 31: ...Omni INSTALLATION INSTRUCTIONS Electrical Installation 3...
Page 53: ...Omni INSTALLATION INSTRUCTIONS Networking 4...
Page 74: ...Omni INSTALLATION INSTRUCTIONS Commissioning 5...