Page 61
Omni Installation Instructions
© Mass Electronics Pty Ltd 2017
Chapter 4 – Networking
2. After the connection has been made, you can now connect to your Omni controller using a
supported browser by navigating to the address,
169.254.2.100
. Assuming the controller
does not previously have a configuration installed, login using the default credentials.
Username: Innotech, Password: 1111. If the controller contains a configuration, login using
user credentials contained in the configuration.
Figure 4-3:
Login Screen Accessed Using USB
3. After logging in, navigate to
Settings > Protocols > BACnet
to edit the BACnet instance (must
be unique).
4. Click Update to save the settings then navigate to
Settings > Port Assignment > Ethernet
to
edit the TCP/IP settings for your controller. Click Update when finished.
Figure 4-4:
BACnet and Ethernet Settings
The password 1111 is only valid for 'blank' controllers, that is blank controllers with newly installed firmware. Focus
software
will not
allow the transfer of a configuration with the password 1111.
Summary of Contents for Omni C14
Page 1: ...Omni INSTALLATION INSTRUCTIONS...
Page 11: ...Omni INSTALLATION INSTRUCTIONS Preliminary Information 1...
Page 17: ...Omni INSTALLATION INSTRUCTIONS Mechanical Installation 2...
Page 31: ...Omni INSTALLATION INSTRUCTIONS Electrical Installation 3...
Page 53: ...Omni INSTALLATION INSTRUCTIONS Networking 4...
Page 74: ...Omni INSTALLATION INSTRUCTIONS Commissioning 5...