Configuration

Fire detection and extinguishant system

Due to the fact that each FPMEXT front plate module is associated automatically with 5 internal IFMEXT modules at
precise addresses, the FPMEXT modules must have an address which respects the IFMEXT - FPMEXT module association
table which follows:

On returning to the control-panel configuration section, the assigned address (

[D]

) will be shown at the side of the

previously selected internal module.

2.5

Setting the network address (IFMNET)

If the installation has control panels connected in a  network, it will be necessary to assign the network address
to each control panel.

Select the IFMNET module in the section on the left containing the internal layout of the cabinet (

[A]

). In the section

which appears, enter the network address and the bit rate.

Note:

Each control panel in the same  network must be set with the same bit rate and univocal
address.

2.6

Addressing the repeaters

The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the
modules and the control panel.

Connection via Ethernet network

The Ethernet connection needs network parameters setting. The procedure must be done via the display of the module
itself, following the indications described in the 

paragraph 2.2 Setting the IP network address

.

Connection via RS485 BUS

The BUS connection needs the addressing of any repeater in configuration,
in order for the control panel to identify each module individually.

To assign an address to a repeater, it is necessary to enter the configuration
procedure starting from the display of the module itself, as described in the

paragraph 2.3

.

A window will open, select the desired address in the programming field,
then tap on 

Set

. The available addresses are from 1 to 14.

Addressing the extinction module

IFMEXT

FPMEXT

IFMEXT

FPMEXT

IFMEXT

FPMEXT

1

1

11

3

21

5

2

1

12

3

22

5

 

3

1

13

3

23

5

4

1

14

3

24

5

 

5

1

15

3

6

2

16

4

7

2

17

4

8

2

18

4

9

2

19

4

10

2

20

4

Address

14

Esc

Set

Summary of Contents for PREVIDIA MAX

Page 1: ...Configuration manual 1 FIRE DETECTION AND EXTINGUISHANT SYSTEM MANUAL FOR SYSTEM CONFIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 0051 0051 CPR 1863 cert N 991K...

Page 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Page 3: ...network address IFMNET 10 2 6 Addressing the repeaters 10 2 7 Enrolling loop devices IFM2L 11 2 8 Acquiring the configuration 13 2 9 Signal check and fault search 13 2 10 Factory data 13 2 11 Setting...

Page 4: ...4 Table of contents Fire detection and extinguishant system...

Page 5: ...ont of the mounted device Qualified personnel Personnel whose training expertise and knowledge of the products and laws regarding security systems are capable of creating in accordance with the requir...

Page 6: ...nalling LEDs activate alarm signalling when an early warning process is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequat...

Page 7: ...3 4 Assign addresses to the system modules paragraph 2 4 5 Enroll loop devices on IFM2L modules and respective troubleshooting procedure paragraph 2 7 6 Set the defined configuration paragraph 2 8 7 C...

Page 8: ...n which appears on the screen The network parameters screen will be shown F Beside these there is the Backup panel option G If enabled the FPMCPU module you are using will be set as control panel back...

Page 9: ...ternal IFM modules on the left A FPM front plate modules on the right F A window will open H select the desired address in the programming field then tap on Set Note Addresses which exceed the maximum...

Page 10: ...and univocal address 2 6 Addressing the repeaters The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the modules and the control panel Connection via...

Page 11: ...nsumption mA 15 LOOP CLOSED Generic 1 Detectors 44 IN Modules 12 OUT Modules 5 IN OUT Modules 0 Sounder flashers 3 Call points 8 Loop reset Scan Show topology Esc Access level 2 01 01 2020 18 23 Loop...

Page 12: ...en by updating the alarm and fault indications of the devices shown restored fault events will not be shown L Button to perform a scan which will search the loop for devices and their serial numbers a...

Page 13: ...ttons on the back of the FPMCPU front plate module Press and hold the Factory data button A and press and release the Reset button B Following confirmation of the request to reset to the factory data...

Page 14: ...required revision of Previdia STUDIO configuration software SW site specific data release Data progressive number of system configuration upgrades FPMLED FPMPRN FPMEXT front plate modules the module...

Page 15: ...aller Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 5 Press the Regist...

Page 16: ...the information provided is clear Ensure that the descriptions of the various zones points and system elements entered during the data entry phase are correct and that the information provided on the...

Page 17: ...Turn On LED buttons Note Testing devices by means of manual activation does not test functionality and efficiency of the cause effect association which determines their activation programming coheren...

Page 18: ...check for the presence of fault or alarm conditions which must be investigated 4 2 Testing the detectors As well as the tests which must be performed during the commissioning phase paragraph 3 2 Testi...

Page 19: ...Configuration manual 19...

Page 20: ...m Centobuchi via Dei Lavoratori 10 63076 Monteprandone AP Italy Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate numbe...

Reviews: