14

Configuration

Fire detection and extinguishant system

2.12

Firmware revision

The installer of Previdia Max system can see the firmware revision of each control panel module in order to facilitate any
upgrade or configuration procedure.

Such information can be achieved depending on the type of the module:

FPMCPU front-plate module:  

by means

of the 

System status

 button on the

display in the stand-by condition, you
can access a section where it is possible
to view the status of the various system
elements.
In the lower left corner of this section 

[A]

you can see:

• serial number of the FPMCPU module
• counter of the number of alarms 

starting from system installation

• firmware version of the FPMCPU 

module (FW, both the main and the 
emergency backup CPU.)

• minimum required revision of Previdia/

STUDIO configuration software (SW)

• site specific data release (Data), 

progressive number of system 
configuration upgrades

FPMLED, FPMPRN, FPMEXT front-plate 
modules:  

the module firmware revision is

written on a label on the back of the module

[B]

; the label can be seen by opening the

cabinet door when the module is already
installed.

IFM internal modules:  

the firmware of

each internal module (already installed)
can be seen by accessing to the
configuration menu (

paragraph 2.3

).

The address and the firmware revision of
the detected modules are shown in the
proper section 

[C]

.

Control panel

Dialer

Zones

I/O Lines

Points

Extinction modules

Groups

Cloud

Timer

SN:SNSNSNSN    Alarm counter: ccc
FW001FPMCPU - FW:xxxxxxxxxxxxx - SW:yy.yy.yy - Data:zzz

Esc

Access level:1

01/01/2020

18:23

A

FW0000FPMxxx

1.00

SBQC0000INxxx

QC

PASSED

NNNN NNN-NN MMMM-MM DD/MM/YYYY

B

N.01 FW:1.0.0.

N.02 FW:1.0.0.

N.12 FW:1.0.0.

Set

Esc

Access 

level:3

01/01/2020

18:23

C

C

C

Summary of Contents for PREVIDIA MAX

Page 1: ...Configuration manual 1 FIRE DETECTION AND EXTINGUISHANT SYSTEM MANUAL FOR SYSTEM CONFIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 0051 0051 CPR 1863 cert N 991K...

Page 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Page 3: ...network address IFMNET 10 2 6 Addressing the repeaters 10 2 7 Enrolling loop devices IFM2L 11 2 8 Acquiring the configuration 13 2 9 Signal check and fault search 13 2 10 Factory data 13 2 11 Setting...

Page 4: ...4 Table of contents Fire detection and extinguishant system...

Page 5: ...ont of the mounted device Qualified personnel Personnel whose training expertise and knowledge of the products and laws regarding security systems are capable of creating in accordance with the requir...

Page 6: ...nalling LEDs activate alarm signalling when an early warning process is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequat...

Page 7: ...3 4 Assign addresses to the system modules paragraph 2 4 5 Enroll loop devices on IFM2L modules and respective troubleshooting procedure paragraph 2 7 6 Set the defined configuration paragraph 2 8 7 C...

Page 8: ...n which appears on the screen The network parameters screen will be shown F Beside these there is the Backup panel option G If enabled the FPMCPU module you are using will be set as control panel back...

Page 9: ...ternal IFM modules on the left A FPM front plate modules on the right F A window will open H select the desired address in the programming field then tap on Set Note Addresses which exceed the maximum...

Page 10: ...and univocal address 2 6 Addressing the repeaters The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the modules and the control panel Connection via...

Page 11: ...nsumption mA 15 LOOP CLOSED Generic 1 Detectors 44 IN Modules 12 OUT Modules 5 IN OUT Modules 0 Sounder flashers 3 Call points 8 Loop reset Scan Show topology Esc Access level 2 01 01 2020 18 23 Loop...

Page 12: ...en by updating the alarm and fault indications of the devices shown restored fault events will not be shown L Button to perform a scan which will search the loop for devices and their serial numbers a...

Page 13: ...ttons on the back of the FPMCPU front plate module Press and hold the Factory data button A and press and release the Reset button B Following confirmation of the request to reset to the factory data...

Page 14: ...required revision of Previdia STUDIO configuration software SW site specific data release Data progressive number of system configuration upgrades FPMLED FPMPRN FPMEXT front plate modules the module...

Page 15: ...aller Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 5 Press the Regist...

Page 16: ...the information provided is clear Ensure that the descriptions of the various zones points and system elements entered during the data entry phase are correct and that the information provided on the...

Page 17: ...Turn On LED buttons Note Testing devices by means of manual activation does not test functionality and efficiency of the cause effect association which determines their activation programming coheren...

Page 18: ...check for the presence of fault or alarm conditions which must be investigated 4 2 Testing the detectors As well as the tests which must be performed during the commissioning phase paragraph 3 2 Testi...

Page 19: ...Configuration manual 19...

Page 20: ...m Centobuchi via Dei Lavoratori 10 63076 Monteprandone AP Italy Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate numbe...

Reviews: