3.2

Testing to detectors and manual activations

All the installed detectors must be tested during the commissioning phase. It is necessary to check the capacity of each
detector to react to a simulated condition of fire, and to check the precision of the signals transmitted to the control
panel in response to its activation (description of the point and zone).

For this purpose it is possible to use the 

Test

 button of the control panel (

[A]

)

on the “Zone status” screen, accessible via the “System status” menu on the
home page.

By tapping this button it is possible to place one or more zones in test status.
The activation of a detector which belongs to a zone in test status will not
generate any alarm signalling or activate the outputs or signalling devices.
However, the control panel will activate the signalling LEDs on the detectors
and will perform automatic reset after a few seconds without any need of
further intervention by the operator on the control panel.

The activation of a point which belongs to a zone in test status will be recorded in the events log. Therefore, on
completion of the test on all the zone devices, the operator can check the congruence of the various indications by
means of the log.

The activation of all the manual call points (alarm buttons) must be tested in the same way as described for the detectors.

3.3

Testing signalling and activations

The functionality and efficiency of all the signalling devices must be checked
thoroughly.

It is possible to test such devices by activating the relative LEDs and outputs
manually at the control panel via the respective management page (

[B]

).

To reach this page you must access the “Points” section via the “System
status” menu on the homepage. Select the desired loop and point to be
tested from the lists shown then, by means of the relative 

View

 buttons go

to the management screen where you will find the 

Turn On output

 and 

Turn

On LED

 buttons.

Note:

Testing devices by means of manual activation does not test functionality and efficiency of the cause/
effect association which determines their activation (programming coherence of groups), therefore, it is
necessary to perform real functionality tests.

3.4

Testing the extinction system

Particular attention must be paid to the testing of eventual fire extinction systems.

Special attention must be paid to the functionality and safety of the extinguishing-agent release devices before
proceeding with the testing of all activation and stop-extinction procedures in accordance with the requirements of the
executive project.

3.5

Maximum time settings. Normative restrictions

During programming via the Previdia/STUDIO software you can set the time length or delay of many control panel
functions. The normative reference standards require maximum duration for the following parameters:

Prealarm time

, the maximum delay time is 10min (EN 54-2 - clause 7.11.1 (c)).

Verification time OFF (s)

, if the verification function is enabled for an input device, the time for which the device 

remains deactivated after the first activation must be 60 seconds maximum (EN 54-2 - clause 7.12.1 [b]).

Verification time (s)

, if an input device has the alarm verification option enabled, the maximum verification time is 30 

minutes (EN 54-2 - clause 7.12.1 [c]).

Lock reset time after released (min)

, the maximum time is 30 minutes (EN 12094-1:2003 - clause 4.12.2).

Pre-extinction time on automatic/manual activation

, the maximum time is 60 seconds (EN 12094-1:2003 - clause 

4.17.2).

Valve ON time

, the maximum time is 300 seconds (EN 12094-1:2003 - clause 4.21).

Refer to the Previdia/STUDIO software programming manual for more details about the parameters listed above.

Zone status

N.

Description

Status

1

Zone 01

Stand-by

2

Zone 02

Fault

3

Zone 03

Stand-by

4

Zone 04

Stand-by

5

Zone 05

Alarm

6

Zone 06

Stand-by

Disable

Test

Esc

Access 

level:2

01/01/2020

18:23

A

Loop module: 03 Point: 03 SNSNSNSNSN
Optical heat det.
Zone 02

Detector lost

Replace

Info

Turn On output

Real-time

Turn On LED

Camera

Disable point

Map

Disable zone

Esc

Access 

level:2

01/01/2020

18:23

B

Summary of Contents for PREVIDIA MAX

Page 1: ...Configuration manual 1 FIRE DETECTION AND EXTINGUISHANT SYSTEM MANUAL FOR SYSTEM CONFIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 0051 0051 CPR 1863 cert N 991K...

Page 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Page 3: ...network address IFMNET 10 2 6 Addressing the repeaters 10 2 7 Enrolling loop devices IFM2L 11 2 8 Acquiring the configuration 13 2 9 Signal check and fault search 13 2 10 Factory data 13 2 11 Setting...

Page 4: ...4 Table of contents Fire detection and extinguishant system...

Page 5: ...ont of the mounted device Qualified personnel Personnel whose training expertise and knowledge of the products and laws regarding security systems are capable of creating in accordance with the requir...

Page 6: ...nalling LEDs activate alarm signalling when an early warning process is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequat...

Page 7: ...3 4 Assign addresses to the system modules paragraph 2 4 5 Enroll loop devices on IFM2L modules and respective troubleshooting procedure paragraph 2 7 6 Set the defined configuration paragraph 2 8 7 C...

Page 8: ...n which appears on the screen The network parameters screen will be shown F Beside these there is the Backup panel option G If enabled the FPMCPU module you are using will be set as control panel back...

Page 9: ...ternal IFM modules on the left A FPM front plate modules on the right F A window will open H select the desired address in the programming field then tap on Set Note Addresses which exceed the maximum...

Page 10: ...and univocal address 2 6 Addressing the repeaters The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the modules and the control panel Connection via...

Page 11: ...nsumption mA 15 LOOP CLOSED Generic 1 Detectors 44 IN Modules 12 OUT Modules 5 IN OUT Modules 0 Sounder flashers 3 Call points 8 Loop reset Scan Show topology Esc Access level 2 01 01 2020 18 23 Loop...

Page 12: ...en by updating the alarm and fault indications of the devices shown restored fault events will not be shown L Button to perform a scan which will search the loop for devices and their serial numbers a...

Page 13: ...ttons on the back of the FPMCPU front plate module Press and hold the Factory data button A and press and release the Reset button B Following confirmation of the request to reset to the factory data...

Page 14: ...required revision of Previdia STUDIO configuration software SW site specific data release Data progressive number of system configuration upgrades FPMLED FPMPRN FPMEXT front plate modules the module...

Page 15: ...aller Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 5 Press the Regist...

Page 16: ...the information provided is clear Ensure that the descriptions of the various zones points and system elements entered during the data entry phase are correct and that the information provided on the...

Page 17: ...Turn On LED buttons Note Testing devices by means of manual activation does not test functionality and efficiency of the cause effect association which determines their activation programming coheren...

Page 18: ...check for the presence of fault or alarm conditions which must be investigated 4 2 Testing the detectors As well as the tests which must be performed during the commissioning phase paragraph 3 2 Testi...

Page 19: ...Configuration manual 19...

Page 20: ...m Centobuchi via Dei Lavoratori 10 63076 Monteprandone AP Italy Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate numbe...

Reviews: