INIM Electronics PREVIDIA MAX Manual For System Configuration, Commissioning And Maintenance Download Page 11

Configuration manual

Configuration

11

Attention:

The “0” address is reserved to the main FPMCPU module. Do not use.

2.7

Enrolling loop devices (IFM2L)

The operations required for the configuration of the IFM2L network modules involve the configuration of the devices
connected to the loops.

The selection of the module from the internal layout section of the cabinet (

paragraph 2.1 Access to programming

,

 [A]

)

will access the configuration section which, in addition to providing the change address button (at the top) also provides
two identical sections for each of the two loops (connected to the Loop-A and Loop-B terminals). The present
document describes the operations necessary for the configuration of a single loop, however, it is implicit that the
operations be repeated for each of the two loop.

[A]

Button to access the section for IFM2L module address assignment (

paragraph 2.4 Addressing IFM 

and FPM modules

).

[B]

Sections containing the configuration menu of the single loops.

Section on the left for the loop connected to the Loop-A terminals, on the right for the Loop-B terminals.

Update

Esc

Access 

level:2

01/01/2020

18:23

001

002

003

004

005

006

007

008

009

010

013

014

015

016

017

018

K

023

024

025

Loop1: Loop1

Loop O terminal: OK
Loop I terminal:
Loop consumption (mA): 15
LOOP CLOSED

Generic: 1
Detectors: 44
IN Modules: 12
OUT Modules: 5
IN/OUT Modules: 0
Sounder/flashers: 3
Call points: 8

Loop reset

Scan

Show topology

Esc

Access 

level:2

01/01/2020

18:23

Loop module

Change address

Loop 1

Loop 2

Diagnostics

Diagnostics

Parameters

Parameters

Auto-configure

Auto-configure

Esc

Access 

level:2

01/01/2020

18:23

A

B

C
D

B

E

F

G

I

H

J

J

C
D
E

C

Acquire

Readdress

Update

Add/Change

Esc

E

L

M

N

O

Procedure in progress
Procedure completed
Found: 73

100%

1 Generic
44 Detectors
12 IN modules
5 OUT modules
0 IN/OUT modules
3 Detectors
8 Call points

Diagnostics

Esc

Access 

level:3

01/01/2020

18:23

Found: 72

N.

SN

Type

Description

SN

Type

1

010EE4D4

Opt. det.

Opt. det. 01

010EE4D4

Opt. det.

2

010EE4E0

Opt. det.

Opt. det. 02

010EE4E0

Opt. det.

3

010EE0AB

IN IN

Input module 01

010EE0AB

Opt. det.

4

010C7CAC

Call 
point

Button 01

5

010E1CE0

Opt. det.

Opt. det. 03

010E1CE0

Opt. det.

6

010EE6F2

Opt. det.

Opt. det. 04

010EE6F2

Opt. det.

Esc

7

010ECC90

Opt. det.

Opt. det. 05

010ECC90 Opt. det.

8

010EFF12

IN IN

Ok

9

010E122C

IN IN

Input module 03

010E122C

IN IN

Access 

level:3

01/01/2020

18:23

Delete

N. SN

Type

Description

1

010EE4D4

Opt. det.

Opt. det. 01

Add/Change

2

010EE4E0

Opt. det.

Opt. det. 02

3

010EE0AB

IN IN

Input module 01

Program

4

010C7CAC Call point

Button 01

5

010E1CE0

Opt. det.

Opt. det. 03

6

010EE6F2

Opt. det.

Opt. det. 04

7

010ECC90

Opt. det.

Opt. det. 05

Esc

8

010EFF12

IN IN

Input module 01

Access 

level:3

01/01/2020

18:23

O

L

M

N

C

Change address

Summary of Contents for PREVIDIA MAX

Page 1: ...Configuration manual 1 FIRE DETECTION AND EXTINGUISHANT SYSTEM MANUAL FOR SYSTEM CONFIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 0051 0051 CPR 1863 cert N 991K...

Page 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Page 3: ...network address IFMNET 10 2 6 Addressing the repeaters 10 2 7 Enrolling loop devices IFM2L 11 2 8 Acquiring the configuration 13 2 9 Signal check and fault search 13 2 10 Factory data 13 2 11 Setting...

Page 4: ...4 Table of contents Fire detection and extinguishant system...

Page 5: ...ont of the mounted device Qualified personnel Personnel whose training expertise and knowledge of the products and laws regarding security systems are capable of creating in accordance with the requir...

Page 6: ...nalling LEDs activate alarm signalling when an early warning process is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequat...

Page 7: ...3 4 Assign addresses to the system modules paragraph 2 4 5 Enroll loop devices on IFM2L modules and respective troubleshooting procedure paragraph 2 7 6 Set the defined configuration paragraph 2 8 7 C...

Page 8: ...n which appears on the screen The network parameters screen will be shown F Beside these there is the Backup panel option G If enabled the FPMCPU module you are using will be set as control panel back...

Page 9: ...ternal IFM modules on the left A FPM front plate modules on the right F A window will open H select the desired address in the programming field then tap on Set Note Addresses which exceed the maximum...

Page 10: ...and univocal address 2 6 Addressing the repeaters The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the modules and the control panel Connection via...

Page 11: ...nsumption mA 15 LOOP CLOSED Generic 1 Detectors 44 IN Modules 12 OUT Modules 5 IN OUT Modules 0 Sounder flashers 3 Call points 8 Loop reset Scan Show topology Esc Access level 2 01 01 2020 18 23 Loop...

Page 12: ...en by updating the alarm and fault indications of the devices shown restored fault events will not be shown L Button to perform a scan which will search the loop for devices and their serial numbers a...

Page 13: ...ttons on the back of the FPMCPU front plate module Press and hold the Factory data button A and press and release the Reset button B Following confirmation of the request to reset to the factory data...

Page 14: ...required revision of Previdia STUDIO configuration software SW site specific data release Data progressive number of system configuration upgrades FPMLED FPMPRN FPMEXT front plate modules the module...

Page 15: ...aller Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 5 Press the Regist...

Page 16: ...the information provided is clear Ensure that the descriptions of the various zones points and system elements entered during the data entry phase are correct and that the information provided on the...

Page 17: ...Turn On LED buttons Note Testing devices by means of manual activation does not test functionality and efficiency of the cause effect association which determines their activation programming coheren...

Page 18: ...check for the presence of fault or alarm conditions which must be investigated 4 2 Testing the detectors As well as the tests which must be performed during the commissioning phase paragraph 3 2 Testi...

Page 19: ...Configuration manual 19...