INIM Electronics PREVIDIA MAX Manual For System Configuration, Commissioning And Maintenance Download Page 8

8

Configuration

Fire detection and extinguishant system

2.1

Access to programming

To access the programming phase of the Previdia Max control panel, it is
necessary to work through the following procedure:

1.

Insert the programming jumper on the back of the FPMCPU module
(see opposite, 

[D]

).

2.

Tap on the 

Programming

 button on the screen (see above, 

[A]

).

3.

A keypad will appear (see opposite, 

[E]

) for the entry of a code with

installation privileges.

Note:

The default access code to level 3 is “00004”.

4.

You access the programming menu, where the following items are
available:

- Configuration
- Network
- Factory data

2.2

Setting the IP network address

If an Ethernet network connection is used, it will be necessary to set up the IP address and parameters of the network.

This operation must be done for anyone of the following devices:

• The Previdia Max control panel, via the main FPMCPU module
• the backup FPMCPU module, via the FPMCPU module itself
• the FPMCPU repeater module, when connected to an Ethernet network, via the FPMCPU module itself

In order to set the network parameters, it is first necessary to access the
programming phase of the control panel (

paragraph 2.1

) and then tap on the

Network

 button which appears on the screen.

The network parameters screen will be shown

 [F]

.

Beside these there is the 

Backup panel

 option

 [G]

. If enabled, the FPMCPU

module you are using will be set as control panel backup CPU unit. In this
case, the network parameters must be the same as the parameters set for
the main FPMCPU module.

Once set, it will be necessary to tap on the 

Ok

 button and save the data.

If the module has been set as a backup CPU unit, the message "In backup" will appear on the display

In the same section you have the tools to register the control panel to the installer profile at the Inim Cloud service 

[H]

(refer to 

paragraph 2.13 Registration of the control panel to Inim Cloud

).

2.3

Accessing the configuration menu

To access the configuration menu it is necessary to first access the programming phase of the control panel (

paragraph

2.1

) and then tap on the 

Configure

 button which appears on the screen.

Alternatively, it is possible to tap directly on the configuration status icon (see above, 

[C]

).

Entry of a valid access code is necessary In both cases.

Once the configuration menu has been accessed, the control panel screen will provide a layout of the control panel and
its parts.

D

00004

1

2

3

A

B

4

5

6

C

D

7

8

9

E

F

C

0

OK

E

Net-
work

IP

192

192

1

1

Backup panel

Netmask

Cloud enabled

255

255

255

0

Enroll

Gateway

192

1

1

1

Esc

Port

6001

Ok

Access 

level:3

01/01/2020

18:23

G

F

H

Summary of Contents for PREVIDIA MAX

Page 1: ...Configuration manual 1 FIRE DETECTION AND EXTINGUISHANT SYSTEM MANUAL FOR SYSTEM CONFIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 0051 0051 CPR 1863 cert N 991K...

Page 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Page 3: ...network address IFMNET 10 2 6 Addressing the repeaters 10 2 7 Enrolling loop devices IFM2L 11 2 8 Acquiring the configuration 13 2 9 Signal check and fault search 13 2 10 Factory data 13 2 11 Setting...

Page 4: ...4 Table of contents Fire detection and extinguishant system...

Page 5: ...ont of the mounted device Qualified personnel Personnel whose training expertise and knowledge of the products and laws regarding security systems are capable of creating in accordance with the requir...

Page 6: ...nalling LEDs activate alarm signalling when an early warning process is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequat...

Page 7: ...3 4 Assign addresses to the system modules paragraph 2 4 5 Enroll loop devices on IFM2L modules and respective troubleshooting procedure paragraph 2 7 6 Set the defined configuration paragraph 2 8 7 C...

Page 8: ...n which appears on the screen The network parameters screen will be shown F Beside these there is the Backup panel option G If enabled the FPMCPU module you are using will be set as control panel back...

Page 9: ...ternal IFM modules on the left A FPM front plate modules on the right F A window will open H select the desired address in the programming field then tap on Set Note Addresses which exceed the maximum...

Page 10: ...and univocal address 2 6 Addressing the repeaters The procedure to configure the FPMCPU modules as repeaters depends on the type of connection between the modules and the control panel Connection via...

Page 11: ...nsumption mA 15 LOOP CLOSED Generic 1 Detectors 44 IN Modules 12 OUT Modules 5 IN OUT Modules 0 Sounder flashers 3 Call points 8 Loop reset Scan Show topology Esc Access level 2 01 01 2020 18 23 Loop...

Page 12: ...en by updating the alarm and fault indications of the devices shown restored fault events will not be shown L Button to perform a scan which will search the loop for devices and their serial numbers a...

Page 13: ...ttons on the back of the FPMCPU front plate module Press and hold the Factory data button A and press and release the Reset button B Following confirmation of the request to reset to the factory data...

Page 14: ...required revision of Previdia STUDIO configuration software SW site specific data release Data progressive number of system configuration upgrades FPMLED FPMPRN FPMEXT front plate modules the module...

Page 15: ...aller Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 5 Press the Regist...

Page 16: ...the information provided is clear Ensure that the descriptions of the various zones points and system elements entered during the data entry phase are correct and that the information provided on the...

Page 17: ...Turn On LED buttons Note Testing devices by means of manual activation does not test functionality and efficiency of the cause effect association which determines their activation programming coheren...

Page 18: ...check for the presence of fault or alarm conditions which must be investigated 4 2 Testing the detectors As well as the tests which must be performed during the commissioning phase paragraph 3 2 Testi...

Page 19: ...Configuration manual 19...

Page 20: ...m Centobuchi via Dei Lavoratori 10 63076 Monteprandone AP Italy Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate numbe...

Reviews: