80448418 Rev.C
1
Airend Discharge Temperature –
The temperature of
the air/oil mixture at the discharge of the compression
module��
After-cooler Discharge Temperature (
Not available
on this compressor model)
–
The temperature of the
air after passing through the After-cooler�� Note that
this will only be shown if the Low Ambient option has
been purchased and installed��
After-cooler Discharge Pressure (integrated dryer
units only) (
Not available on this compressor
model)
–
Pressure the compressor is delivering before
the dryer��
Page 2 – Compressor Data
Figure 24 : Compressor data
Compressor Data:
Power ON Hours –
The number of hours the controller
has been powered up
Running Hours –
The number of hours the
compressor’s motor has been running
Loaded Hours -
The number of hours the compressor
has been producing air
Real Time Clock -
Current time of day
Pages 3 and 4 – Digital Inputs
Figure 25 : Digital inputs
•
•
•
•
•
•
•
Digital Inputs:
Each digital input will have an indication showing
whether the input is in an “OPEN” or “CLOSED” state�� This
is the physical state of the input and may not necessarily
line up with the logical condition�� The normal state is
shown below��
Emergency Stop –
Normally Closed
Main/Fan Motor Overload –
Normally Closed
Remote Load Enable –
Normally Open
Remote Load/Unload –
Normally Open
Remote Start -
Normally Open
Remote Stop –
Normally Closed
Dryer Temperature Fault –
Normally Open
Dryer High Pressure –
Normally Closed
Pages 5 and 6 – Digital Inputs
Figure 26 : Digital inputs
Digital Outputs:
Each digital output will have an indication showing
whether the output is in an “OPEN” or “CLOSED” state�� This
is the physical state of the input and may not necessarily
line up with the logical condition�� The normal state is
shown below��
Starter Contact KM1, KM2 –
Normally Open
Starter Contact KM3 –
Normally Open
Fan Starter Contact KM4 –
Normally Open
Load Solenoid 1SV –
Normally Open
Modulation Solenoid 3SV –
Normally Open
Dryer Run / Fan Run –
Normally Open
PORO Horn –
Normally Open
Trip Indication –
Normally Open
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
OPERATING INSTRUCTIONS (XE-70M CONTROLLER)
RELEASED 20/Jul/2016 17:56:55 GMT
Summary of Contents for UP5S 11
Page 34: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 35: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 36: ...ingersollrandproducts com 2016 Ingersoll Rand RELEASED 20 Jul 2016 17 56 55 GMT...
Page 74: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 75: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 76: ...ingersollrandproducts com 2016 Ingersoll Rand RELEASED 20 Jul 2016 17 56 55 GMT...
Page 114: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 115: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 116: ...ingersollrandproducts com 2016 Ingersoll Rand RELEASED 20 Jul 2016 17 56 55 GMT...
Page 153: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 154: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 155: ...RELEASED 20 Jul 2016 17 56 55 GMT...
Page 156: ...ingersollrandproducts com 2016 Ingersoll Rand RELEASED 20 Jul 2016 17 56 55 GMT...