9.0 OPERATING INSTRUCTIONS
9.7 OPTIONS
Options are turned on or off and their associated values
are set using the OPTION screen shown opposite.
Some options are purchased, they require additional
machine hardware and must first be enabled by service
personnel. The name and value of each of the following
options can be seen by moving the list up and down
using the arrow buttons.
An Option item’s value can be changed the same way that
OPERATOR SETPOINTS values are changed.
−OPTIONS−
100
PSI
100
PSI
REMOTE START/STOP ON
READY TO START
REMOTE START/STOP ON
STATUS
MAIN MENU
SELECT
OPTIONS Items
SELECTION
MIN.
MAX.
Step
Unit
Installed
Option
Required
Remote Pressure
Sensor
ON/OFF
No
Sequencer
ON/OFF
No
Remote Start/Stop
ON/OFF
No
Power Out Restart
ON/OFF
Yes
Power Out Restart Time
10
600
1
SEC
Yes
Scheduled Start Day
day
day
1
day
Yes
Scheduled Start
00:00
23:59
1
time
Yes
Scheduled Stop Day
day
day
1
day
Yes
Scheduled Stop
00:00
23:59
1
time
Yes
Modbus Protocol
ON/OFF/ICU
No
Modbus Address
1
247
1
No
Remote pressure sensor
If this setting is set to ON, the compressor will use
a remote mounted pressure sensor for controlling
system pressure by comparing it to the Target Pressure
setting and the Auto Stop Pressure setting. The pressure
measured by this sensor is shown in the CURRENT STATUS
display as the Remote Pressure reading. The local sensor
at the package discharge is still used for Immediate Stop,
for certain Alarm conditions and for display on the left
side of the screen.
Sequencer
If this setting is set to ON, the compressor will be able to
start and stop by commands from a host device. When
the Intellisys receives a load command from the host
device, the compressor will start. When the Intellisys
receives an unload command the compressor will
respond as though executing an immediate stop.
Remote start/stop
If this setting is set to ON, the compressor can be started
and stopped from a remote device.
Power out restart
If this setting is set to ON, the compressor will
automatically restart when power is returned to the
compressor if it was operating when power was removed.
Note:
A kit including instruction manual is required to install
this option.
Power out restart time
If the power out restart setting is set to ON, this is the
number of seconds from the time power is restored until
the compressor starts. The power out restart horn will
sound during this time.
Scheduled start day
This option is the selection for the day that a scheduled
start will take place. The selections are Sunday, Monday,
Tuesday, Wednesday, Thursday, Friday, Saturday, Daily (Su-
Sa), Weekdays (M - F), or Weekends. This option setpoint
will work with the scheduled start setpoint.
111213.14.59