When using high inertia or low resistive torque machines, the user should initiate a controlled stop. To achieve a
controlled stop in accordance with stop category 1 of the EN60204-1 standard, the control system of the machine
must generate the following sequences:
-
deceleration of the load by means of the drive,
-
when the load is at standstill or almost, shutting down of the PWM by disabling the "enable/inhibit signal"
using the appropriate digital input or network signal when connected,
-
finally, activation of the STO function.
STOP
0
1
SPEED
0
0
1
ENABLE
24V
STO1
0
STO2
Deceleration ramp is
controlled by the drive