GD1 – Installation Guide
Part 3 -
Appendix
2.2.2
–
STO
CONNECTION
X2 N°
SIGNAL
FUNCTION
DESCRIPTION
7
IN7
STO1
Channel 1 for the STO function inhibition
24 Vdc releases the enabling
6
IN6
STO2
Channel 2 for the STO function inhibition
24 Vdc releases the enabling
16
0 V internal
GND internal
20
0 V external
GND external
Voltage reference of the STO1 and 2 inputs.
0 V internal and 0 V external must be connected
together.
25 STO_OUT- STO_OUT-
26
NC dry contact for the display of the STO1 input state.
24 Vdc – 2 A
During the installation, take care to avoid proximity between any STO signal and high potential.
2.2.3
–
TIMINGS
The STO function is based on forcibly guided relay technology. Its response time is given by the typical Operate
Time/Release Time of the relay: 12 ms / 20 ms.
Refer to the following chronogram for more detailed explanation:
The STO function has two feedbacks: the "STO_OUT" contact and detailed state available in object 0x3001. Only
the output "STO_OUT" is a safe output. An incoherent state detected between inputs STO1 and STO2 leads to a
fault state.
Used alone, the STO function corresponds to an uncontrolled stop in accordance with stop category 0 of the
EN60204-1 standard. So, this function is suitable for machines with low inertia or high resistive torque.
STO_OUT
t
≤
50ms
t
≤
50ms
t
>
50ms
20ms
12ms
Ready Safe
Ready
Safe
Fault state
STO1
STO2
Drive
state
Close
Open
Summary of Contents for GD1-400/05
Page 1: ...GD1 INFRANOR Gem Drive Installation Guide gb Actuator ...
Page 5: ...4 Part 1 GD1 amplifier GD1 Installation Guide PART 1 ________ GD1 AMPLIFIER ...
Page 40: ...GD1 Installation Guide 39 Part 2 GDPS power supply PART 2 ________ GDPS POWER SUPPLY ...
Page 49: ...48 Part 2 Chapter 4 Order code GD1 Installation Guide PART 3 ________ APPENDIX ...