3.17 COMBUSTION PARAMETERS.
G20
G30
G31
Zeus 24 kW
Gas nozzle diameter
mm
1.35
0.79
0.79
Supply pressure
mbar (mm H
2
O)
20 (204)
29 (296)
37 (377)
Flue flow rate at nominal heat output
kg/h
49
50
51
Flue flow rate at minimum heat output
kg/h
53
50
50
CO
2
at Q. Nom./Min.
%
7.5 / 2.7
8.5 / 3.3
8.2 / 3.3
CO at 0% of O
2
at Q. Nom./Min.
ppm
86 / 66
70 / 84
45 / 80
NO
X
at 0% of O
2
at Q. Nom./Min.
ppm
123 / 71
161 / 84
165 / 80
Flue temperature at nominal heat output
°C
108
109
107
Flue temperature at minimum heat output
°C
87
91
91
Zeus 28 kW
Gas nozzle diameter
mm
1.35
0.79
0.79
Supply pressure
mbar (mm H
2
O)
20 (204)
29 (296)
37 (377)
Flue flow rate at nominal heat output
kg/h
56
56
57
Flue flow rate at minimum heat output
kg/h
60
57
58
CO
2
at Q. Nom./Min.
%
7.70 / 2.86
9.00 / 3.47
8.70 / 3.42
CO at 0% of O
2
at Q. Nom./Min.
ppm
158 / 101
184 / 109
105 / 108
NO
X
at 0% of O
2
at Q. Nom./Min.
ppm
54 / 28
67 / 37
74 / 35
Flue temperature at nominal heat output
°C
110
114
111
Flue temperature at minimum heat output
°C
87
91
90