System commands
Restore Factory
Settings
Restore Factory Settings�
Empty teach
Empty adjustment, automatically sets the switching thresholds
SP and rP� More information:
(→ 9.1)
�
Full teach
Full adjustment to the medium, automatically sets the switching
thresholds SP and rP� More information:
(→ 9.1)
�
Reset
[Hi�T] and [Lo�T]
Reset maximum and minimum value memory�
Flash On
Visual indication (double flash) for localisation ON.
The indication automatically disappears after 1 minute�
Flash Off
Visual indication (double flash) for localisation OFF.
For further information, please refer to the IODD description (→ www.ifm.com)
or to the context-specific parameter descriptions of the used parameter setting
software�
9.2.5 Example parameter setting via IO-Link
►
Set the switching output OUT2 to temperature measurement�
Example: [SEL2] = [TEMP]
►
The temperature output OUT2 shall be set as alarm output (as normally closed
with a high temperature threshold). Example: [ou2] = [Hnc]
►
Set the alarm temperature to 80°C�
Example: [SP2 (FH2)-TEMP] = 80;
[rP2 (FL2)-TEMP] = 75.
►
Transfer the sensor data to the unit�
►
Carry out a full adjustment to the medium to be detected:
Fill the tank until the active zone (A
→ 6.3) of the unit is completely covered.
►
Execute the system command [full teach]�
All other settings remain as set at the factory�