14
9.1.3 Set for full tank condition
In case of aqueous media, in particular those where deposits or soiling are to be
expected, the empty adjustment is not necessary and a full adjustment can be
carried out immediately�
Where an empty adjustment has been carried out for aqueous media, it
must be followed by a full adjustment to achieve a perfect adjustment of
the unit sensitivity to the medium�
1
►
Fill the tank until the active zone (A
→ 6.3) is
completely covered�
2
►
Unlock the unit
(→ 9.1.1)
3
►
Actuate the teach button for at least 4 s / not
longer than 7 s�
> First, the green LED3 goes out briefly, then the
two yellow LEDs start flashing slowly after 1 s
(at approx. 1 Hz) before flashing quickly after 4 s
(at approx. 2 Hz).
► Release the teach button (remove metal object).
> Successful completion of the full adjustment is
acknowledged with a double flash of the green
LED (at approx. 2 Hz).
While the unit is in factory setting, both yellow
LEDs are lit�
> The unit is ready for operation�
While the unit is in factory setting, output
1 (OUT1) is set to normally open and output
2 (OUT2) to normally closed.
Modify output configuration:
(→ 9.2)
�