17
UK
SP2 (FH2) - TEMP
Switch point 2 or upper temperature limit for window function
([SEL2]=[TEMP]).
[SP2 (FH2)] must be greater than [rP2 (FL2)].
If [SP2 (FH2)] is set to a value below [rP2 (FL2)], this is
rejected by the device software�
rP2 (FL2) - TEMP
Switch point 2 or lower temperature limit for window function
([SEL2]=[TEMP]).
dS1 / dS2
Switching delay
4
) for OUT1 and OUT2.
Setting range 0�0���10�0 s
dr1 / dr2
Switching delay
4
) for OUT1 and OUT2.
Setting range 0�0���10�0 s
FOU1 / FOU2
Response of OUT1 or OUT2 in case of a fault:
[OFF] = switching output switches OFF in case of a fault�
[On] = switching output switches ON in case of a fault�
[OU] = switching output reacts according to process value,
if possible�
Lo�T
Minimum value memory for the temperature
Hi�T
Maximum value memory for the temperature
Unit locking�
Local parameter setting
[Open] = parameter setting via teach button is permitted�
[Locked] = parameter setting via teach button is locked�
1)
This setting is not possible in combination with [ou2] = [Fno] or [Fnc]�
2
) This setting is only possible in combination with [SEL2] = [TEMP].
3
) Tap water in grounded metal tank
4)
Response according to VDMA� According to VDMA the switch-on delay always has an
effect on SP, the switch-off delay always on rP irrespective of whether the normally open or
normally closed function is used�