15BError messages
107BSystem errors: error codes R01...R30 (RTS errors)
16-16
Error message
Cause(s)
Solution
R06
General RTS program failure
The operating system has detected an
invalid status in the process while exe-
cuting the program internally.
Possible cause: operating system soft-
ware error.
►
Reinstall the operating system
R07
Master not in the "Projection mode"
The attempt was made to execute an
AS-i command which is only permitted
in the "Projection Mode".
►
Switch the master to the operating
mode "Projection mode".
→
page 10-2, chapter 10.2 "How are
the operating modes for the AS-i master
changed?"
R08
No PLC program loaded
The attempt was made to start a PLC
program although no program has been
loaded in the controllere.
►
Load PLC program into the control-
lere:
→
page 11-4, chapter "Connecting the
R09
RS-232C transmission error (baud rate)
detected
The hardware of the integrated serial
interface chip has found a transfer error
in the RS-232C data flow.
Possible causes:
3. Baud rate setting in the controllere
different from the setting in the PC.
4. Other programs (e.g. messenger)
send via the RS-232 interface of the
PC
On 1:
►
Adjust baud rate:
→
page 11-1, chapter 11.1 "Setting the
baud rate of the serial interface"
On 2:
►
Stop other programs on the PC
R10
RS-232C buffer overflow detected
A buffer overflow was detected in the
serial receive buffer of the RS-232C
interface.
Possible causes:
1. RS-232 message too long or baud
rate too high.
2. Faulty connection cable between
PC and RS-232C connection on the
controllere
On 1:
►
Check the driver or reduce the baud
rate
On 2:
►
Replace connection cable
R11
RS-232C parity check failed
The parity check of the serial data flow
of the RS-232C interface was unsuc-
cessful.
Possible cause: electromagnetic inter-
ference
►
Reduce interference on the RS-232
cable by means of the following
measures:
- screen the cable
- reduce the cable length
- remove the interfering source