15BError messages
106BSystem errors: error codes M01...M20 (AS-i master command errors)
16-12
Error message
Cause(s)
Solution
M07
Writing to slave failed
1. The attempt of the master to read-
dress a slave to the new target ad-
dress fails.
2. Writing the "Extended ID Code 1" to
slave 1 fails.
Example: attempt to readdress an
A/B slave to another address.
►
Repeat the command
M08
New address only stored temporarily
During the readdressing of a slave the
new address could no longer be written
on the slave because the slave is no
longer detected on the AS-i bus.
Possible causes:
1. Double addressing
2. Major bus interference
On 1:
►
Remove one of the slaves with
double address
►
Readdress the remaining slave
►
Reactivate the removed slave
On 2:
►
Remove the cause of the error
M09
Extended ID1 temporarily stored
While writing the "ID Code 1" to the
slave the code could not be written to
the slave because the slave is no longer
detected on the AS-i bus.
Possible causes:
1
Double addressing
2
Major bus interference
On 1:
►
Remove one of the slaves with
double address
►
Readdress the remaining slave
►
Reactivate the removed slave
On 2:
►
Remove the cause of the error
M10
Slave not in the LAS
The master detects that a slave has not
been activated.
Possible causes: the slave profile in the
projection data is not identical with the
profile of the detected slave and the
master is in the "Protected Mode".
►
Switch the master to the operating
mode "Projection mode".
→
page 10-2, chapter10.2 “How are the
operating modes for the AS-i master
changed?"
►
Check and replace the slave
►
Project slaves again:
"Menu" > "Quick Setup"
→
page11-15, chapter "End configura-