15BError messages
103BProcess error: error codes E10...E30 (AS-i system)
16-5
Error message
Cause(s)
Solution
E22
Slave 0 detected
The master is in the "Protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is identical to the profile of the slave
with the address 0.
►
Switch master to the operating
mode "Projection mode".
→
page 10-2, chapter 10.2 "How are
the operating modes for the AS-i master
changed?"
E23
Slave 0 has wrong profile
The master is in the "Protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is not identical to the profile of the
slave with the address 0.
►
Check and replace slave
►
Project slaves again:
"Menu" > "Quick Setup"
→
page 11-15, chapter "End configura-
E24
Automatic addressing not activated
The master is in the "Protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is identical to the profile of the slave
with the address 0, and the "Automatic
Addressing" in the master, however,
was not activated.
►
Activate "Automatic addressing" in
the master:
→
page 11-8, chapter "Automatic indi-
E25
Projection error of the master
The master is in the "Normal operating
mode" and detects a projection error.
Possible causes:
•
The profiles of the detected slaves
are not identical to the projected
slaves.
•
One or more slaves are additionally
detected on the AS-i bus.
•
One or several slaves are missing
on the AS-i bus.
►
Check the detected and projected
slave profile in the menu "Slave
Info".
→
page 13-48, chapter 13.22 "Display
►
Check the entries of the slaves in
the lists LAS, LDS, LPS, LPF in the
menu "Slave Lists".
→
page 13-3, chapter 13.3 "Display of
→
page 13-5, chapter 13.4 "Display of
→
page 13-8, chapter 13.5 "Display of
→
page 13-11, chapter 13.6 "Display of
slaves with peripheral fault (list)"
E26
Peripheral fault detected on the AS-i
bus
The master is in the "Normal operating
mode" and detects that at least one
slave on the AS-i bus signals a periph-
ery fault.
→
page 13-11, chapter 13.6 "Display of
slaves with peripheral fault (list)"
→
page 13-14, chapter 13.7 “Display