Adjustable parameters
32
Technical information / Operation / Parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SPx is only active if
OUx
=
Hno
,
Hnc
,
Fno
or
Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching
status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automa-
tically reduced (rPx is set to the minimum setting value).
rPx is only active if
OUx
=
Hno
,
Hnc
,
Fno
or
Fnc.
Setting ranges:
in steps of
l/min
0.1
0.1 ... 50.0
0.0 ... 49.9
m
3
/h
0.005
0.005 ... 3.000
0.000 ... 2.995
SP1 / SP2
rP1 / rP2
in steps of
SP2
rP2
°C
+5.2 ... +80.0
+5.0 ... +79.8
0.2
Pulse setting
Determines the pulse value indicating the volume to which one
pulse corresponds.
Setting range
: 0.001 [m
3
] ... 100
×
10
3
[ m
3
].
After the value 9999 10.00 is displayed and the LED
10³
flashes.
Pulse length: min. 0.5 s / max. 2 s.
ImPS
is only active if OU1 =
ImP.
Pulse repetition
Determines which signals are provided by the meter at output 1,
2 settings can be selected:
•
YES
: Pulse repetition active (= simple counter function):
Output 1 provides a counting pulse every time the value set in
ImPS
is reached.
•
no
: Pulse repetition not active (the counter operates as a pre-
set counter): Output 1 switches (OUT1 = ON) when the value
set in
ImPS
is reached. It remains switched until the counter is
reset (
→
page 36, parameter
rTo
).
ImPR
is only active if OU1 =
ImP.