35
ENGLISH
Output polarity
2 options can be selected:
PnP
= positive switching,
nPn
= negative switching.
This setting applies to both switching outputs.
Damping of the measured value
• Setting range: 0 (= dAP not active) - 0.2s - 0.4s - 0.6s - 0.8s - 1s.
The setting influences display and outputs.
Factory setting: 0.6 s .
Setting of the display
7 settings can be selected:
•
d1
= update of the measured value every 0.5 sec.
•
d2
= update of the measured value every 1 sec.
•
d3
= update of the measured value every 2 sec.
The update interval only refers to the display. It has no effect on
the outputs.
•
rd1
,
rd2, rd3
= display as for d1, d2, d3, but rotated by 180°.
•
OFF
= In the Run mode the display of the measured value is
deactivated.
If one of the pushbuttons is pressed, the current measured value
is displayed for 15 s. Another press of the Mode/Enter pushbut-
ton opens the Display mode.
The switching status LEDs remain active even if the display is
deactivated.
Factory setting:
d2
.
Reset of the meter
•
M
anual reset:
The meter is manually erased and a new metering interval
starts:
- Press the "Set" pushbutton until
rES.T
is indicated.
- Then briefly press the "Mode/Enter" pushbutton.
A manual reset can also be carried out if a period is set for
automatic reset.
•
OFF
= reset after overflow of the meter (= after 100 000 m³).
• Time-controlled automatic reset
After a defined period the meter is automatically erased and a
new metering interval starts.
The following periods can be set:
-
1 h
...
23 h
(reset after 1 ... 23 hours, setting in steps of 1h),
-
1 d
...
6 d
(reset after 1 ... 6 days, setting in steps of 1d),
-
1 w
...
8 w
(reset after 1 ... 8 weeks, setting in steps of 1w).