33
ENGLISH
Analogue start point
Measured value at which 4 mA / 0 V is provided.
ASP is only active if OU2 =
I
or
U
.
Analogue end point
Measured value at which 20 mA / 10 V is provided.
Minimum distance between ASP and AEP = 20% of the final
value of the measuring range.
AEP is only active if
OU2
=
I
or
U
.
Setting ranges:
in steps of
l/min
0.1
0.0 ... 40.0
10.0 ... 50,0
m
3
/h
0.005
0.000 ... 2.400
0.600 ... 3.000
ASP
AEP
°C
+5.0 ... +65.0
+20.0 ... +80.0
0.2
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET pushbut-
ton briefly.
Configuration of output 1
5 settings can be selected:
- Output signals for flow rate:
•
Hno
= hysteresis function / normally open
•
Hnc
= hysteresis function / normally closed
•
Fno
= window function / normally open
•
Fnc
= window function / normally closed
- Output signal for the meter:
•
ImP
= Pulse sequence or On / Off signal for preset counter
(
→
page 32 / parameter
ImPS
and
ImPR
)
Configuration of output 2
4 switching functions and 2 analogue signals can be set for flow
rate or temperature (
→
page 36 / parameter
SEL2
):
•
Hno
= hysteresis function / normally open
•
Hnc
= hysteresis function / normally closed
•
Fno
= window function / normally open
•
Fnc
= window function / normally closed
•
I
= analogue signal (4 ... 20 mA)
•
U
= analogue signal (0 ... 10 V)