Object directory
Manufacturer Specific Profile Area; index 2000 to 5FFF
ENGLISH
Input/output module CR2013
29
Index S-idx Designation
Type
Default
Description
2000
0
I/O
configuration
u8, ro
0x08
Number of the entries (= number of the I/O
channels)
1
I/O
channel 1*
u8, rw
0x01
0 = OFF
1 = binary input
2
I/O
channel 2*
u8, rw
0x02
0 = OFF
2 = binary output
3 = analog input
4 = analog output (PWM)
3
I/O
channel 3*
u8, rw
0x01
0 = OFF
1 = binary input
4
I/O
channel 4*
u8, rw
0x02
0 = OFF
2 = binary output
3 = analog input
4 = analog output (PWM)
5
I/O
channel 5*
u8, rw
0x01
0 = OFF
1 = binary input
6
I/O
channel 6*
u8, rw
0x02
0 = OFF
2 = binary output
3 = analog input
4 = analog output (PWM)
7
I/O
channel 7*
u8, rw
0x01
0 = OFF
1 = binary input
8
I/O
channel 8*
u8, rw
0x02
0 = OFF
2 = binary output
3 = analog input
4 = analog output (PWM)
2001
0
PWM
Frequency
u8, rw
0x64
(= 100 Hz)
Setting in Hz
Range = 20Hz to 200Hz
Values below 20Hz or above 200Hz are not
accepted. The existing value remains valid.
2002
0
Output
monitoring
ON / OFF
u8, rw
0x01
0 = OFF
Short circuit, overload, output open (no load),
undervoltage, overvoltage or too high a tempera-
ture is neither indicated by EMCY nor by LED.
1 = ON
In the case of a short circuit, overload, output
open (no load), undervoltage, overvoltage or
too high a temperature on an output the corre-
sponding EMCY object is transferred, the out-
put LED flashes.
(The switching threshold for "output open" can
be as high as an output current of
900 mA).
*Values which cannot be assigned to the channels are not accepted.
2003
0
Filter
function
ON / OFF
u8, rw
0x00
0 = OFF
On the binary inputs
switching pulses
≥
2 ms are detected.
1 = ON
On the binary inputs
switching pulses
≥
20 ms are detected.