2: D
EVICES
2-36
FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
■
D8170, D8171, D8174, D8175, D8178, D8179: Analog I/O Cartridge I/O
Analog I/O values for the analog
I/O
cartridges are written to these registers.
For details, see Chapter 10 "Analog I/O Cartridge" in the "FC6A Series MICROSmart User’s Manual".
D8170 = AI2/AQ2
D8171 = AI3/AQ3
D8174 = AI4/AQ4
D8175 = AI5/AQ5
D8178 = AI6/AQ6
D8179 = AI7/AQ7
■
D8172, D8173, D8176, D8177, D8180, D8181: Analog I/O Cartridge Status
The analog status of analog I/O cartridges is written to these registers.
For details, see Chapter 10 "Analog I/O Cartridge" in the "FC6A Series MICROSmart User’s Manual".
D8172 = AI2/AQ2
D8173 = AI3/AQ3
D8176 = AI4/AQ4
D8177 = AI5/AQ5
D8180 = AI6/AQ6
D8181 = AI7/AQ7
■
D8192 to D8203, D8210 to D8213, D8216 to D8229, D8232 to D8237: High-speed Counter
These special data registers are used with the high-speed counter function and the frequency measurement function.
For details on high-speed counters, see Chapter 5 "High-Speed Counter" in the "FC6A Series MICROSmart User’s Manual".
D8210 to D8213, D8216, D8217 = High-speed counter (group 1/I0)
D8218 to D8221, D8234, D8235 = High-speed counter (group 3/I3)
D8222 to D8225, D8236, D8237 = High-speed counter (group 4/I4)
D8226 to D8229, D8232, D8233 = High-speed counter (group 5/I6)
D8192 to D8197 = High-speed counter (group 2/I1)
D8198 to D8203 = High-speed counter (group 6/I7)
■
D8239: Absolute Position Control Status
This register indicates the status of absolute position control.
The allocation of the absolute position counter initialized flags in the device (bit assignment) is as follows. For details on the
absolute position control status, see "ABS (Set Absolute Position)" on page 18-68.
■
D8240 to D8247: Absolute Position Counter 1 to 4
The absolute position is written to these registers according to pulse output. The absolute position can be initialized with the
ABS instruction.
When reversible control is set in the pulse output instructions (RAMP/ARAMP/ZRN/JOG), the absolute position is incremented or
decremented according to the output result. For details on absolute position counters, see "ABS (Set Absolute Position)" on page
18-68.
D8240, D8241 = Absolute position counter 1
D8242, D8243 = Absolute position counter 2
D8244, D8245 = Absolute position counter 3
D8246, D8247 = Absolute position counter 4
■
D8250: Read SD Memory Card Capacity
This register indicates the capacity of the recognized SD or SDHC (maximum size 32 GB) memory card in megabytes.
For the analog input type
: The analog values input to the analog
I/O
cartridge are converted to digital values and written to
the registers.
For the analog output type : The digital values stored as digital values are converted to analog values and output from the
analog I/O cartridges.
Bit
15
Bit
0
Bit
7
Bit
8
1
2
3
Absolute Position Counter 1 Initialized Flag
Absolute Position Counter 2 Initialized Flag
Absolute Position Counter 3 Initialized Flag
Absolute Position Counter 4 Initialized Flag
0: Not initialized
1: Initialized
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Page 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...