FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
5-17
5: M
OVE
I
NSTRUCTIONS
XCHG (Exchange)
Valid Devices
For valid device address ranges, see "Device Addresses" on page 2-1.
Special internal relays cannot be designated as D1 or D2.
Valid Data Types
Examples: XCHG
• Data Type: Word
• Data Type: Double Word
Word data:
D1
↔
D2
Double-word data:
D1·D1+1
→
D2, D2+1
When input is on, the 16- or 32-bit data in devices assigned by D1 and D2 are exchanged with
each other.
XCHG(*)
D1
*****
D2
*****
Device
Function
I
Q
M
R
T
C
D
P
Constant
Repeat
D1 (Destination 1)
First device address to exchange
—
X
X
—
—
X
—
—
—
D2 (Destination 2)
First device address to exchange
—
X
X
—
—
X
—
—
—
W (word)
X
When a bit device such as Q (output), M (internal relay), or R (shift register) is assigned as the destination, 16
points (word data) or 32 points (double-word data) are used.
When a word device such as D (data register) is assigned as the destination, 1 point (word data) or 2 points
(double-word data) are used.
I (integer)
—
D (double word)
X
L (long)
—
F (float)
—
D21
↔
D24
When input I0 is turned on, data of data registers D21
and D24 assigned by devices D1 and D2 are exchanged
with each other.
I0
XCHG(W)
D2
D24
D1
D21
SOTU
D22
1000
D21
D23
Before Exchange
After Exchange
2000
D24
D22
2000
D21
D23
1000
D24
D31·D32
↔
D37·D38
When input I1 is turned on, data of data registers
D31·D32 and D37·D38 assigned by devices D1 and D2
are exchanged with each other.
I1
XCHG(D)
D2
D37
D1
D31
SOTU
Before Exchange
After Exchange
1234567890
D31·D32
D33·D34
D35·D36
9876543
D31·D32
D33·D34
D35·D36
9876543
D37·D38
1234567890
D37·D38
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Page 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...