![background image](http://html1.mh-extra.com/html/ics/multipanel-2025/multipanel-2025_manual_3540033024.webp)
Error codes
24
O
perati
ng Instruct
ions
• Version
1.0
ERROR CODES
TECHNICAL DATA
Code
Description
8100
Error in flash memory during read and
write test
8101
Flash memory could not be deleted
8102
General error with flash memory
(e.g. flash memory not detected)
8106
Calibration interval:
Reminder of the next calibration
Reminder of the next calibration,
page 22
8107
Calibration interval:
Calibration interval is not set
8108
Calibration interval:
Calibration interval has been exceeded
8114
Range:
Upper and lower limit values are inverted.
8110
Zero adjustment not possible
Current measurement value > 1% max.
measurement series
Property
Value
Dimensions (H x W x D)
96 x 96 x 60mm
Weight
298 g
Temperature range
-20...+50 °C
Relative humidity
0...80%
Protection class
IP 40
Measurement channels
Analogue input signal
0/4...20 mA
0/2...10 V
Tolerances
±0.2% FS
Frequency input signal
1 Hz...5 kHz
Tolerances
±0.1% MW