PN
Function
Range of value
De-
fault
User-
level
95
Type of delay
0 = none
1 = switching-on delay
2 = switching-off delay
3 = switching-on/-off delay
0
5
Linearisation
100
Number of additional switchpoints
0…30
0
2
101
to
130
Switchpoints 1…30
-9999…99999
2
System information (not adjustable)
200
Serial number
0…99999
0
8
204
Event counter / Configuration counter
0…9999
XXXX
8
33
9. Reset to default values
To return the unit to a defined basic state, a reset can be carried out to the default
values.
The following procedure should be used:
• Switch off the power supply
• Press button
[P]
• Switch on the power supply and press
[P]
for approx. further 2 seconds.
With reset, the default values of the program table are loaded and used for subsequent
operation. This puts the unit back to the state in which it was supplied.
Caution!
•
This is only possible when the programming lock PN50 allows access to all
program numbers (PNs) or "
HELP
" is shown in the display.
•
All application-related data are lost.
9. Reset to default values