![ICS IPM5 User Manual Download Page 6](http://html1.mh-extra.com/html/ics/ipm5/ipm5_user-manual_3538998006.webp)
Output
Relay
Switchover contact
250 VAC / 5A; 30 VDC / 5 A at ohm resistive burden
Switching cycle
0.5 * 10
5
at maximum contact load
5 * 10
6
mechanically
Division according to DIN EN 50178/Characteristics according to DIN EN 60255
Analog output
(galvanic isolated)
0/4-20 mA / burden <500
Ω
,
0-10 VDC burden
≥
10 k
Ω
, 16 bit
Error
0.1 % in a range of T
U
= 20…40 °C, outside of 50 ppm/K
Bridge supply
approx. 10 VDC / 200-500
Ω
, standard 350
Ω
Interface
Protocol
manufacturer specific ASCII
RS232
9600 Baud, no parity, 8 data bit, 1 stop bit
Cable length
max. 3 m
RS485
9600 Baud, no parity, 8 data bit, 1 stop bit
Cable length
max. 1000 m
Power pack
Voltage supply
100-240 VAC / 50/60 Hz, DC ± 10% (max. 15 VA)
10-40 VDC galv. isolated, 18-30 VAC / 50/60 Hz (max. 15 VA)
Memory
Parameter memory EEPROM
Data life
≥
100 years at 25°C
Ambient conditions
Working temperature
0…50°C
Storing temperature
-20…80°C
Weathering resistance
relative humidity
≤
75% on years average without dew
EMV
DIN 61326
CE-sign
conformity according directive 2004/108/EG
Safety standard
according to low voltage directive 2006/95/EG;
EN61010; EN60664-1
4
2. Technical data