8.1 Program number description
The program table lists all the program numbers (PN) with their function, range of values, default
values and user level.
PN
Function
Range of value
De-
fault
User-
level
Channel 1
0
Measuring input
Parameter < 5 do not necessarily need a
sensor signal for calibration
Parameter > 4 need a sensor signal for
calibration
0 = automatic sensor detection
1 = semi-automatic sensor detection
2 = 1 mV/V
3 = 2 mV/V
4 = 3.3 mV/V
5 = automatic sensor detection
6 = semi-automatic sensor detection
7 = 1 mV/V
8 = 2 mV/V
9 = 3.3 mV/V
10 = 6 mV/V
10
2
1
Final value / Fullscale
-9999…99999
10000
2
2
Zero point / Offset
-9999…99999
0
2
3
Places after decimal point
0…4
none
2
5
Offset displacement
-9999…99999
0
2
6
Taring function
0 = no taring
1 = permanent taring
2 = transient taring
3 = quick, transient taring without
report
4 = permanent taring onto PN2
5 = static taring at triggering
1
2
7
Set value for taring
A direct taring is carried out, if PN8=0.
-9999…99999
0
4
8
Triggering for taring
0 = none
1 = digital input
2 = 4th key
3 = digital input or 4th key
4 = system start
5 = combination 1 & 4
6 = combinatiom 2 & 4
7 = combination 3 & 4
0
2
9
Calibration mode for automatic operation:
Calibration in % only onto final value PN1
Calibration in PN onto offset PN2 and final
value PN1
0 = autocalibration to %
1 = semi-automatic to %
2 = autocalibration to PN
3 = semi-automatic to PN
4 = start mode 0
5 = start mode 1
6 = start mode 2
7 = start mode 3
2
2
28