2-4
2
9. OEMs may want to change the 9009’s IDN message to report the
OEM’s company and model number (See 3.8.15). Save the new IDN
message and set CAL:LOCK On. The network settings can be left
alone as the end user will need to change them for his company and
location.
2.4.2 9099 Installation Guide
The following steps should be used as to setup and use the 9009.
1. Review Section 2.9 to select or design the serial cable to the Modbus
RTU Slave Device. Change the jumper positions as directed in Sec-
tion 2.10 to match the selected signal type.
2. Connect the AC adapter, serial cable and the Ethernet cable to the unit.
Connect the other end of the Ethernet cable directly to a PC or to the
PC through a switch that is not connected to your network as shown
in Figure 2-2.
8099 Ethernet
to Modbusl
9099 Modbus Interface
Serial IO
RS-232
or
RS-422/RS-485
Ethernet Cable
PC with a Windows
Operating System
Hub or Network Switch
Local Network Connection
Figure 2-2 9099 with Local or benchtop Connection
3. Follow the directions in Section 2.6 for setting the computer to com-
municate with the 9099. Use ICS’s VXI-11kybd program to access
the 9099 at its default IP of 192.168.0.254.
4. Send the 9009 an *IDN? query to readback its IDN message and to
verify communication with the 9009.
5. Review the factory settings in Table 1-2 to determine if the baud rate
or any other settings need to be changed for the Modbus slave device.
Use the ‘D’ command (see Table 3-5) to set the Modbus timeout to
1000 for initial tests.
Summary of Contents for 9099
Page 20: ...1 16 1 Figure 1 1 9009 Outline Dimensions ...
Page 24: ...1 20 1 Figure 1 3 9099 Certificate of Compliance ...
Page 54: ...3 8 3 Figure 3 1 Status Reporting Structure Flash Configuration Reset ...
Page 94: ...3 48 3 This page left intentionally blank ...
Page 100: ...4 4 6 This page is left intentionally blank ...