ICP DAS PMC/PMD Series User Manual
103
front of the pre-set Modbus I/O module and then click on
“Copy”, a new Modbus I/O module (in sequence) will be added
to the list and the settings of the old Modbus I/O module will be
copied to this newly added Modbus I/O module.
Remove: Click the radio button in front of the Modbus I/O
module and click on “Remove” to remove the selected Modbus
I/O module.
After all settings are completed, click “Save” button to save the
changes.
7.3.5
M-7000/DL Module Setting
PMC/PMD support ICP DAS M-7000/DL module, the following
section will give more detailed settings of ICP DAS M-7000/DL
module setting page. (Figure 7-38)
Nickname
:
For user to define nicknames for each M-7000/DL
module, this nickname will be displayed on the “I/O
Information ” and “Rule Setting” pages.
Description: The Description field provides a space for the user
to make a brief description of this M-7000/DL module.
Address: The address will be the Modbus address of this
M-7000/DL module, please make sure the address is the same
as the settings of the module, if the setting is not accurate, the
connection for PMC/PMD to the M-7000/DL module will be
failed.
Scan Rate: Input the time interval for PMC/PMD to periodically
retrieve the I/O channel data of this M-7000/DL module, the
setting range will be 0 ~ 65535 seconds.
Polling Timeout: The time interval for PMC/PMD to send
command to the M-7000/DL module and wait for the response,
the unit will be ms. The setting range will be 1-10000 ms.
Retry Interval: The time interval to wait for PMC/PMD to
repeatedly send command again when PMC/PMD sends
command to the M-7000/DL module and get no response. The
unit will be second. the setting range will be 3 ~ 65535 seconds.
The settings interfaces of the DI, DO, AI and AO channels on the
M-7000/DL Module are as below:
Summary of Contents for PMC series
Page 1: ...ICP DAS PMC PMD Power Meter Concentrator Series User Manual Version 3 1 8...
Page 51: ...ICP DAS PMC PMD Series User Manual 38 Figure5 32 Energy Usage Breakdown by Circuit Group Chart...
Page 72: ...ICP DAS PMC PMD Series User Manual 59 Figure6 11 Security setting interface of VPN function...
Page 165: ...ICP DAS PMC PMD Series User Manual 152 The Import of MQTT Topic...