ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 98
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(80)
1=on
(Default=0)
595
0~31
(32)
Enable/Disable AI channel
1
0=disable
1=enable
(Default=1)
R/W/E
627
1
Temperature Scale
1
0: F
1: C
(Default=0)
R/W/E
628
1
Reserved
629
1
50/60Hz rejection for AI
1
1=50Hz
0=60Hz
(Default=0)
R/W/E
630
1
Reserved
631
1
AI data format
1
0=hex
1=engineering
(Default=0)
R/W/E
632
1
Return the factory calibration (All)
1
1=clear
R/W
(Pulse)
633
Reserved
634
1
Clear AI Latch High (All)
1
1=clear
W
(Pulse)
635
1
Clear AI Latch Low (All)
1
1=clear
W
(Pulse)
636
0~31
(32)
AI Alarm High switch
1
0=disabled
1=enabled
R/W/E
668
0~31
(32)
AI Alarm Low switch
1
0=disabled
1=enabled
R/W/E
700
0~31
(32)
AI Alarm High mode
1
0=Moment
1=Latched
R/W/E
732
0~31
(32)
AI Alarm Low mode
1
0=Moment
1=Latched
R/W/E
764
0~31
(32)
AI High Alarm
1
0=OK
1=alarm
(Clear)
R/W
(Pulse)
796
0~31
(32)
AI Low Alarm
1
0=OK
1=alarm
(Clear)
R/W
(Pulse)