Detailed Modbus Address Table for ET-7017/PET-7017 (D)
(0xxxx) DO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
162
32
Clear AI Latch High
1
1=clear
W
(Pulse)
194
32
Clear AI Latch Low
1
1=clear
W
(Pulse)
347
1
Enable the average value of the
previous AI values of one
channel for all AI
1
0=disable
1=enable
(Default=0)
R/W/E
348
1
Enable average of all enable
channel, High/Low Alarm value of
all AI average value and Average
latched values for all AI channels
1
0=disable
1=enable
(Default=0)
R/W/E
595
8
Enable/Disable AI channel
1
0=disable
1=enable
(Default=1)
R/W/E
628
1
Normal/Fast mode for AI
1
0=normal (16 bit)
1=fast (12 bit)
(Default=0)
R/W/E
629
1
50/60Hz rejection for AI
1
1=50Hz
0=60Hz
(Default=0)
R/W/E
631
1
AI data format
1
1=engineering
0=hex
(Default=0)
R/W/E
632
1
Return the factory calibration (All)
1
1=clear
R/W/E
634
1
Clear AI Latch High (All)
1
1=clear
W
(Pulse)
635
1
Clear AI Latch Low (All)
1
1=clear
W
(Pulse)
636
8
AI Alarm High switch
1
0=disabled
1=enabled
R/W/E
668
8
AI Alarm Low switch
1
0=disabled
1=enabled
R/W/E