Detailed Modbus Address Table for ET-7015/PET-7015 (D)
(0xxxx) DO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
595
7
Enable/Disable AI channel
1
0=disable
1=enable
(Default=1)
R/W/E
629
1
50/60Hz rejection for AI
1
0=50Hz
1=60Hz
(Default=1)
R/W/E
631
1
AI data format
1
1=engineering
0=hex
(Default=0)
R/W/E
632
1
Return the factory calibration (All)
1
1=clear
R/W/E
830
1
Enable/ Disable calibration(All)
1
0=disable
1=enable
R/W
831
1
Zero calibration command of ch0
1
1=run (Pulse)
R/W
832
1
Span calibration command of ch0
1
1=run (Pulse)
R/W
833
1
Zero calibration command of ch1
1
1=run (Pulse)
R/W
834
1
Span calibration command of ch1
1
1=run (Pulse)
R/W
835
1
Zero calibration command of ch2
1
1=run (Pulse)
R/W
836
1
Span calibration command of ch2
1
1=run (Pulse)
R/W
837
1
Zero calibration command of ch3
1
1=run (Pulse)
R/W
838
1
Span calibration command of ch3
1
1=run (Pulse)
R/W
839
1
Zero calibration command of ch4
1
1=run (Pulse)
R/W
840
1
Span calibration command of ch4
1
1=run (Pulse)
R/W
841
1
Zero calibration command of ch5
1
1=run (Pulse)
R/W
842
1
Span calibration command of ch5
1
1=run (Pulse)
R/W
843
1
Zero calibration command of ch6
1
1=run (Pulse)
R/W
844
1
Span calibration command of ch6
1
1=run (Pulse)
R/W