ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 118
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
1=60Hz
(default=1)
631
1
AI data format
1
1=engineering
0=hex
(default=0)
R/W/E
632
1
Return the factory calibration (all)
1
1=clear
R/W
(Pulse)
634
1
Clear AI Latch High (all)
1
1=clear
W
(Pulse)
635
1
Clear AI Latch Low (all)
1
1=clear
W
(Pulse)
636
10
AI Alarm High switch
1
0=disabled
high alarm
1=enabled
high alarm
R/W/E
668
10
AI Alarm Low switch
1
0=disabled
low alarm
1=enabled low
alarm
R/W/E
700
10
AI Alarm High mode
1
0=Moment
1=Latched
R/W/E
732
10
AI Alarm Low mode
1
0=Moment
1=Latched
R/W/E
764
10
AI High Alarm
1
0=OK
1=alarm
(clear)
R/W
(Pulse)
796
10
AI Low Alarm
1
0=OK
1=alarm
(clear)
R/W
(Pulse)
828
1
High Alarm of Average value of all
AI channel
1
0=OK
1=alarm
(clear)
R/W
(Pulse)
829
1
Low Alarm of Average value of all
AI channel
1
0=OK
1=alarm
(clear)
R/W
(Pulse)
830
1
Enable/Disable calibration
1
0=disabled
1=enabled
R/W