ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 93
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
4.3. Modbus Register Map
4.3.1. Common Function
(0xxxx) DO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
226
1
Recover all I/O default
settings
1
1=recover
W
(Pulse)
233
1
Reboot
ET-7000/PET-7000
1
1=reboot
W
(Pulse)
(3xxxx) AI address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
350
1
OS image version
1
123 (hex) means
version=1.2.3
R
351
1
Total Firmware version
1
123 (hex) means
version=1.2.3
R
358
1
Modbus communication
status
1
0= No Error
-1= CRC error
-2= Timeout
R
360
1
Pair Connection
1
0=Normal
1=Timeout
2=Disconnected
R