Detailed Modbus Address Table for ET-7018Z/PET-7018Z
(0xxxx) DO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0
6
Digital Out
1
0=off
1=on
R/W
162
10
Clear AI Latch High
1
1=clear
W
(Pulse)
194
10
Clear AI Latch Low
1
1=clear
W
(Pulse)
347
1
Enable the average value of the
previous AI values of one channel
for all AI
1
0=disable
1=enable
(default=0)
R/W/E
348
1
Enable average of all enable
channel, High/Low Alarm value of
all AI average value and Average
latched values for all AI channels
1
0=disable
1=enable
(default=0)
R/W/E
349
1
Save module nick name to
EEPROM
1
1=write
W
(Pulse)
431
1
Write DO Power On value to
EEPROM
1
1=write
W
(Pulse)
432
1
Write DO Safe value to EEPROM
1
1=write
W
(Pulse)
435
6
Power On value for DO
1
0=off
1=on
(default=0)
R/W/E
515
6
Safe value for DO
1
0=off
1=on
(default=0)
R/W/E
595
10
Enable/Disable AI channel
1
0=disable
1=enable
(default=1)
R/W/E
627
1
Enable/Disable CJC
1
0=Disable
1=Enable
(default=1)
R/W/E
629
1
50/60Hz rejection for AI
1
0=50Hz
R/W/E