CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
135
11-bit COB-ID (bit)
Func Code
Node ID
8-byte Data (byte)
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0
1
2
3 4 5 6 7
1 1 0 0 0 0 0 0 0 0 1
0
8
23 05 16
01
08 01 00
62
SDO client
SDO server
(CAN-8123/CAN-8223/
CAN-8423)
ccs
: 1
n
: 0
e
: 1
s
: 1
m
: 05 16 01
d
: 08 01 00 62
The value “08 01 00 62” means the mapped object is stored in the
index 0x6200 with sub-index 01. It is an 8-bit data unit. Users can
check this object in the Standardize object mapping table described
above. It is mapped to the DO0~DO7 for I-8057.