CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
107
z
Access Digital I/O & Analog I/O
Step 1. In order to change the DO value of the I-8057 to be 0x1234, users must
send the PDO message by using the first RxPDO.
11-bit COB-ID (bit)
Func Code
Node ID
8-byte Data (byte)
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0
1
2
3 4 5 6 7
0 1 0 0 0 0 0 0 0 0 1
0
8
34 12 00
00
00 00 00
00
PDO
producer
PDO consumer
(CAN-8123/CAN-8223/
CAN-8423)
COB-ID
: 0x201
L
: 8
PDO-msg
: 34 12 00 00 00 00
Only the first two bytes are valid, even if the
L
is set to 8, because
the data in the first RxPDO contains only two bytes. According to the
PDO mapping table shown above, the first byte is for the DO0~DO7
channel values of the I-8057. The second byte is for the DO8~DO15
channel values of the I-8057.