Tip 1:
Error Code 12 Potential Causes
Curtain switch is not detected
5 minutes into harvest 3
consecutive times.
Electrical:
•
Is the curtain sensor faulty?
•
Has the curtain magnet fallen off the water curtain?
•
Dose the hot gas valve have power, but it’s not opening?
•
Is the ice thickness probe too close to the evaporator?
IM-Series
Error Codes
43
Refrigeration:
•
Dose the hot gas valve have power, but it’s not opening?