![Ice IMM 8001 User Manual Download Page 96](http://html.mh-extra.com/html/ice/imm-8001/imm-8001_user-manual_609983096.webp)
IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
____________________________________________________________________________________________
IMU307-1 GB Ind. B
94
7 - MAINTENANCE
7. 1. BASIC CASE TEST
The basic case of the relay includes the current and voltage transformers, as well as the associated
protections and loads.
The components are accurate enough to allow interchangeability between various IMM 8000
electronic modules which fit into this basic case.
The analogue signals delivered by the basic case to the electronic module run through two DB9
sockets (female socket on the basic case, male plug on the electronic module).
To test the signals delivered by the transformers, refer to the connection and to the values noted
below.
Signal amplitude and identification
Db9 socket identification
terminals 5 and 9 are connected
- Amplitude
Terminals
Signals
Value
1 - 5/9
I1
1.365 V rms +/- 5 % at IN CT
3 - 5/9
I3
1.365 V rms +/- 5 % at IN CT
4 - 5/9
Io
1.365 V rms +/- 5 % at IN CT position 3CT
1.365 V rms +/- 5 % at IN CT / 10 position ZCT
8 - 5/9
U31
1.54 V rms +/- 5 % at 100V
Terminals
Signals
1
I1
3
I3
4
Io
5/9
0V
8
U13
1
6
9
5