IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
__________________________________________________________________________________________________________________________________________
IMU307-1 GB Ind. B
80
DISPLAY OF UNDER VOLTAGE PROTECTION AFTER AND DURING START ANSI code [27] and [27ST]
PARAMETER SETTING
→
←
STATISTICS
→
←
PARAMETERS
TABLE 1
→
←
PARAMETERS
TABLE 2
→
←
→
←
CURRENTS
46 50 51N 51STL
→
←
VOLTAGES
27 59
→
←
↑
↓
UNDER VOLTAGE
27 27ST 27RC
→
←
27 – U<
1
OFF -- -- -- --
→
←
Operating level
1
U<
0.80 Un
→
←
Time-delay
1
tU<
3.0 s
→
←
27 – Ust<
1
OFF -- -- -- --
→
←
Operating level
1
Ust<
0.80 Un
→
←
Time-delay
tust<
3.0
→
←
RANGES
U<
Ust<
27 – U<
1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
27 – Ust< 1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
Operating level
1
U<
0.80 Un
RANGE : 0.2 to 1.2 Un
STEP : 0.01 Un
Operating level1
Ust<
0.80 Un
RANGE : 0.2 to 1.2 Un
STEP : 0.01 Un
Time-delay
1
tU<
0.1 s
RANGE : 0.1 to 100 s
STEP : 0.1 s
Time-delay 1
tust<
0.1 s
RANGE : 0.1 to 100 s
STEP : 0.1 s