![Ice IMM 8001 User Manual Download Page 89](http://html.mh-extra.com/html/ice/imm-8001/imm-8001_user-manual_609983089.webp)
IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
__________________________________________________________________________________________________________________________________________
IMU307-1 Ind. B
87
DISPLAY OF OVER VOLTAGE PROTECTION ANSI code [59]
PARAMETER SETTING
→
←
STATISTICS
→
←
PARAMETERS
TABLE 1
→
←
PARAMETERS
TABLE 2
→
←
→
←
CURRENTS
46 50 51N 51STL
→
←
VOLTAGES
27 59
→
←
↑
↓
UNDER VOLTAGE
27 27ST 27RC
→
←
OVER VOLTAGE
59
59 – U>
1
OFF -- -- -- --
→
←
Operating level
1
U>
1.10 Un
→
←
Time-delay
1
tU>
3.0 s
→
←
59 – U>>
1
OFF -- -- -- --
→
←
Operating level
1
U>>
1.15 U n
→
←
Time-delay 1
tU>>
0.1
RANGES
59>
1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
59>>
1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
Operating level
1
U>
1.10 Un
RANGE : 0.7 to 1.5 Un
STEP : 0.01 Un
Operating level 1
U>>
1.15 Un
RANGE : 0.7 à 1.5 Un
STEP : 0.01 Un
Time-delay
1
tU>
3.0 s
RANGE : 0.1 to 100 s
STEP : 0.1 s
Time-delay
1
tU>>
0.1 s
RANGE : 0.1 to 100 s
STEP : 0.1 s