Table 10. Sensor information, event description, and service action for the 5104-22C, 9006-12P,
9006-22C, or 9006-22P (continued)
Sensor name (Sensor ID)
Event description
Service action
• FAN1 (0xE3)
• FAN2 (0xE4)
• FAN3 (0xE5)
• FAN4 (0xE6)
• FAN5 (0xE7)
• FAN6 (0xE8)
• FAN7 (0xE9)
• FAN8 (0xEA)
• Transition to Critical from Less
Severe
• Transition to Non-recoverable
from Less Severe
• Transition to Critical from Non-
recoverable
If the sensor name is FAN1,
FAN4, FAN5, or FAN8, no service
action is required. If the sensor
name is FAN2, replace Fan 2. If
the sensor name is FAN3, replace
Fan 3. If the sensor name is
FAN6, replace Fan 6. If the
sensor name is FAN7, replace
identify the physical location and
removal and replacement
procedure.
• Lower Non-critical – going low
• Lower Non-critical – going high
• Lower Critical – going low
• Lower Critical – going high
• Lower Non-recoverable – going
low
• Lower Non-recoverable – going
high
• Upper Non-critical – going low
• Upper Non-critical – going high
• Upper Critical - going low
• Upper Critical - going high
• Upper Non-recoverable – going
low
• Upper Non-recoverable – going
high
• Device Inserted/Device Present
No service action is required.
• Device Removed/Device
Absent
• Transition to degraded
• Install error
• Redundancy lost
• Non-redundant insufficient
resources
Ensure that all fans are seated
identify the physical location and
removal and replacement
procedure.
Beginning troubleshooting and problem analysis 47