Table
3-1 (Page 22 of 40). Firmware Error Codes.
Error Code
Description
Action / Possible Failing FRU
2BA00337
Service Processor reports Memory
Critical Over Temperature Slow
Shutdown request
1. Check for cool air flow obstructions to
the system.
2. Check fans for obstructions that
prevent them from normal operation
(example: a cable caught in the fan
preventing it from spinning)
3. If problem persists, replace Memory
Card.
2BA00338
Service Processor reports Generic
Fast Shutdown request
1. Replace power supply.
2. Replace I/O Board (See notes on 3-1.)
2BA00340
Service Processor reports Locked
fan - Fast Shutdown request fan
number 1
1. Replace fan 1.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
2BA00341
Service Processor reports Locked
fan - Fast Shutdown request fan
number 2
1. Replace fan 2.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
2BA00342
Service Processor reports Locked
fan - Fast Shutdown request fan
number 3
1. Replace fan 3.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
2BA00343
Service Processor reports Locked
fan - Fast Shutdown request fan
number 4
1. Replace fan 4.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
2BA00350
Service Processor reports Generic
Immediate Shutdown request
1. Replace power supply.
2. Replace I/O Board (See notes on 3-1.)
2BA00351
Service Processor reports Generic
AC power loss EPOW
1. Replace power supply.
2. Replace I/O Board (See notes on 3-1.)
2BA00352
Service Processor reports Loss of
AC power (outlet)
1. Replace power supply.
2. Replace I/O Board (See notes on 3-1.)
2BA00353
Service Processor reports Loss of
AC power (power button)
1. Replace power supply.
2. Replace I/O Board (See notes on 3-1.)
2BA00360
Service Processor reports Slow
DASD Fan #1
1. Replace DASD Fan 1.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
2BA00361
Service Processor reports Slow
DASD Fan #2
1. Replace DASD Fan 2.
2. If problem persists, replace power
supply.
3. Replace I/O Board (See notes on 3-1.)
Chapter 3. Error Code to FRU Index
3-23
Summary of Contents for H Series
Page 1: ...RS 6000 Enterprise Server Model H Series IBM Installation and Service Guide SA38 0547 01...
Page 14: ...xiv RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 34: ...1 18 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 108: ...2 74 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 182: ...3 74 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 254: ...6 40 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 285: ...Chapter 7 Removal and Replacement Procedures 7 31...
Page 322: ...7 68 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 323: ...Chapter 8 Parts Information Chapter 8 Parts Information 8 1...
Page 336: ...8 14 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 348: ...A 12 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 422: ...E 28 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 426: ...F 4 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 433: ...Index X 7...
Page 434: ...X 8 RS 6000 Enterprise Server Model H Series Installation and Service Guide...
Page 437: ......