Parameter No.2: Auto switch "LS" signal detection range adjustment
No. Category
Name
Symbol
Unit
Input range
Default setting
at shipping
2
A
Auto switch
"LS" signal
detection
INP
mm
Actuator dependent
to 9999.99
0.10
●
Sets the backward complete/forward complete ON trigger range relative to the
backward end/forward end.
●
When the ELECYLINDER enters the detection range, the backward complete or
forward complete signal turns ON.
●
The minimum setting unit is 0.01mm.
The LS signal detection range for
the conditions below is
shown in the figure.
Backward end: 0.00mm
Forward end: 100.00mm
Parameter No.2 : 0.10mm
Caution
A value smaller than the minimum resolution cannot be set.
Minimum resolution [mm/p] = ball screw lead [mm/r] ÷ 800 [p/r]
Backward end
0.00mm
Forward end
30.00mm
[LS0 detection range]
-0.10 to 0.10mm
[LS1 detection range]
29.90 to 30.10mm
Configuration example
6.4 Parameter function descriptions