Performing maintenance / inspection
FAM 15/30/50/70 ATEX
en(us)
Page 83 / 96
BeWa FAM15-70 Atex 3193049h en(us) 2013-06-19
2013-06-19
Testing the Float Switch in the Oil Pan
Proceed as follows to test the float switch in the oil pan:
1.
Use your fingers to raise the float switch in
the oil pan.
2.
The unit must switch off and the fault
message "Pan overfilled" must appear in
display of the control panel.
3.
Release the float switch and acknowledge
the fault message by pressing the F3 key.
4.
The unit continues to operate -> You have
tested the function of the float switch
positively.
5.
If the unit does not switch off after the
lifting of the float switch and no fault
message appears, contact the HYDAC
Service.